Aviata At Bryan Dairy

Florida Agency for Health Care Administration citation AJ1T-K0920-20240613

Survey date 2024-06-13 - inspection

No Actual Harm, Potential Minimal (CLASS_III)
Corrected
Agency
Florida Agency for Health Care Administration
Citation code
AJ1T-K0920-20240613
Severity
CLASS_III
Survey type
inspection
Source system
fl_ahca

What the regulator cited

ELECTRICAL EQUIPMENT - POWER CORDS AND EXTENS Electrical Equipment - Power Cords and Extension Cords Power strips in a patient care vicinity are only used for components of movable patient-care-related electrical equipment (PCREE) assembles that have been assembled by qualified personnel and meet the conditions of 10.2.3.6. Power strips in the patient care vicinity may not be used for non-PCREE (e.g., personal electronics), except in long-term care resident rooms that do not use PCREE. Power strips for PCREE meet UL 1363A or UL 60601-1. Power strips for non-PCREE in the patient care rooms (outside of vicinity) meet UL 1363. In non-patient care rooms, power strips meet other UL standards. All power strips are used with general precautions. Extension cords are not used as a substitute for fixed wiring of a structure. Extension cords used temporarily are removed immediately upon completion of the purpose for which it was installed and meets the conditions of 10.2.4. 10.2.3.6 (NFPA 99), 10.2.4 (NFPA 99), 400-8 (NFPA 70), 590.3(D) (NFPA 70), TIA 12-5

What this severity rating means

No actual harm with a potential for minimal harm. The least severe class of CMS finding.

Resolution status

Corrected on 2024-07-12.