Aviata At Tallahassee

Florida Agency for Health Care Administration citation JEO4-K0371-20230321

Survey date 2023-03-21 - inspection

No Actual Harm, Potential Minimal (CLASS_III)
Corrected
Agency
Florida Agency for Health Care Administration
Citation code
JEO4-K0371-20230321
Severity
CLASS_III
Survey type
inspection
Source system
fl_ahca

What the regulator cited

SUBDIVISION OF BUILDING SPACES - SMOKE COMPAR Subdivision of Building Spaces - Smoke Compartments 2012 EXISTING Smoke barriers shall be provided to form at least two smoke compartments on every sleeping floor with a 30 or more patient bed capacity. Size of compartments cannot exceed 22,500 square feet or a 200-foot travel distance from any point in the compartment to a door in the smoke barrier. 19.3.7.1, 19.3.7.2 Detail in REMARKS zone dimensions including length of zones and dead-end corridors.

What this severity rating means

No actual harm with a potential for minimal harm. The least severe class of CMS finding.

Resolution status

Corrected on 2023-05-03.