Survey date 2021-06-22 - inspection
SUBDIVISION OF BUILDING SPACES - SMOKE BARRIE Subdivision of Building Spaces - Smoke Barrier Construction 2012 EXISTING Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier. 19.3.7.3, 8.6.7.1(1) Describe any mechanical smoke control system in REMARKS.
No actual harm with a potential for minimal harm. The least severe class of CMS finding.
Corrected on 2021-07-23.