Aviata At University Hills

Florida Agency for Health Care Administration citation PWT5-K0914-20230614

Survey date 2023-06-14 - inspection

No Actual Harm, Potential Minimal (CLASS_III)
Corrected
Agency
Florida Agency for Health Care Administration
Citation code
PWT5-K0914-20230614
Severity
CLASS_III
Survey type
inspection
Source system
fl_ahca

What the regulator cited

ELECTRICAL SYSTEMS - MAINTENANCE AND TESTING Electrical Systems - Maintenance and Testing Hospital-grade receptacles at patient bed locations and where deep sedation or general anesthesia is administered, are tested after initial installation, replacement or servicing. Additional testing is performed at intervals defined by documented performance data. Receptacles not listed as hospital-grade at these locations are tested at intervals not exceeding 12 months. Line isolation monitors (LIM), if installed, are tested at intervals of less than or equal to 1 month by actuating the LIM test switch per 6.3.2.6.3.6, which activates both visual and audible alarm. For LIM circuits with automated self-testing, this manual test is performed at intervals less than or equal to 12 months. LIM circuits are tested per 6.3.3.3.2 after any repair or renovation to the electric distribution system. Records are maintained of required tests and associated repairs or modifications, containing date, room or area tested, and results. 6.3.4 (NFPA 99)

What this severity rating means

No actual harm with a potential for minimal harm. The least severe class of CMS finding.

Resolution status

Corrected on 2023-07-24.