Lakeside Health Center

Florida Agency for Health Care Administration citation 2DHN-K0223-20211214

Survey date 2021-12-14 - inspection

No Actual Harm, Potential Minimal (CLASS_III)
Corrected
Agency
Florida Agency for Health Care Administration
Citation code
2DHN-K0223-20211214
Severity
CLASS_III
Survey type
inspection
Source system
fl_ahca

What the regulator cited

DOORS WITH SELF-CLOSING DEVICES Doors with Self-Closing Devices Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke barrier, or hazardous area enclosure are self-closing and kept in the closed position, unless held open by a release device complying with 7.2.1.8.2 that automatically closes all such doors throughout the smoke compartment or entire facility upon activation of: * Required manual fire alarm system; and * Local smoke detectors designed to detect smoke passing through the opening or a required smoke detection system; and * Automatic sprinkler system, if installed; and * Loss of power. 18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8

What this severity rating means

No actual harm with a potential for minimal harm. The least severe class of CMS finding.

Resolution status

Corrected on 2022-01-14.